Ultrasonic Flow Meters

20+ Years Manufacturing Experience

RC82 Series Ultrasonic Heat Meter DN15-40

Short Description:

RC82 Series ultrasonic heating (cooling, heating-cooling) meters are used for energy measurement of heating or chilled water in residential and small commercial heating and air conditioning systems. They are available in DN15-40 and have an electronic energy calculator with separate register for heating and cooling energy. They are fitted with an M-Bus interface for integration into M-Bus networks.


RC82 Series ultrasonic heating (cooling, heating-cooling) meters are used for energy measurement of heating or chilled water in residential and small commercial heating and air conditioning systems. They are available in DN15-40 and have an electronic energy calculator with separate register for heating and cooling energy. They are fitted with an M-Bus interface for integration into M-Bus networks.

Features

feature-ico01

Internal 3.6V lithium battery power supplying;

feature-ico01

Calculator case's unique design, users can meet multi-angle data is read;

feature-ico01

Support supply water and backwater pipeline position installation to satisfy users different requirements. 

feature-ico01

Support level and vertical installation to satisfy users’ different requirements.

feature-ico01

Support optical interface, RS485 interface and M-Bus interface etc. multi-communication mode, easy for centralized data management by user.

feature-ico01

NOWA-testing in the parallel mode is applicable.

Technical Data

Profile

Application Heating/cooling/heating-cooling metering
Approval MID
Mount position Vertical or horizontal
Calculator protection class IP 65
Battery supply 3.6V lithium battery up to 8 years lifetime
Temperature sensor type PT1000
Cable length of temperature sensor 1.5 meter (or customized)
Test possibilities display, instruction (compatible with NOWA software)

Calculator basic features

Environmental class EN1434/MID E1+M1
Ambient operating temperature A Class (5~55) ℃ or B Class(-25 ~ +55) ℃ optional
Ambient storage temperature -20~ +70 ℃
Protection class IP 65
Radio system Wireless M-bus can be integrated by 868,434,169MHz (OMS)
Standard interface Optical interface
Interfaces optional 1 Slots for modules with M-Bus, RS485, Pulse Output
Temperature range heating 4~95℃
Temperature range cooling 4~95℃
Extensive data memory 720 days flow data and heat data
RS485 communication red is vcc(5~24VDC),white is B,green is A,black is GND
Pulse output red is output and black is GND

 

Display

Display indication LCD, 8 digits
Units MWh - kWh - GJ - Gcal - ℃ –K - m³ - m³/h
Total values 99,999,999 - 9,999,999.9 - 999,999.99 - 99,999.999
Values displayed Energy /Power/Volume/ Flow Rate/Temperature and more

 

Interfaces

Optical Band rate 2400
M-Bus Band rate 300-9600
RS485 Band rate 300-9600
Pulse output One pulse output

 

Temperature input

Starting temperature difference ∆Θ K 0.25
Min. temperature difference ∆Θmin K 3 (2K can be customized)
Max. temperature difference ∆Θmax K 60 (105 can be customized)
Absolute Temperature measuring range Θ ℃ 4 ~95 (4-130 can be customized)

 

 

Dimension

Screw thread connection version
thread 1
Nominal Flow rate Qp m3/h 0.6 0.6 0.6 1.5 3.5 6 6 10
Nominal Diameter DN mm 15 20 20 15 25 25 32 40
Body Length L mm 110 130 190 110 160 260 180/260 200/300
Overall Length L2 mm 200 230 290 200 260 360 280/360 300/400
Calculator Length L1 mm 150 150 150 150 150 150 150 150
Height H 100 103 103 100 106 106 109 113
Calculator Height H1 60 60 60 60 60 60 60 60
Calculator Width B 105 105 105 105 105 105 105 105
Screw thread on meter inch G3/4B G1/4B G1B G3/4B G1 1/4B G1 1/4B G1 1/2B G2B
Screw thread on coupling inch R1/2 R3/4 R3/4 R1/2 R1 R1 R1 1/4 R1 1/2
Working pressure Mpa 1.6/2.5
Qp: Qi 50:1, 100:1, 250:1
flange 1
Nominal Flow rate Qp m3/h 0.6 1 1.5 2.5 3.5 6 6 10
Nominal Diameter DN mm 20 20 20 20 25 25 32 40
Overall Length L mm 190 190 190 190 260 260 260 300
Calculator Length L1 mm 150 150 150 150 150 150 150 150
Height H 47.5 47.5 47.5 47.5 52.5 52.5 62.5 70
Height 1 H1 103 103 103 103 106 106 109 109
Calculator Height H2 60 60 60 60 60 60 60 60
Calculator Width B 105 105 105 105 105 105 105 105
Flange Diameter F mm 95 95 95 95 105 105 125 140
Flange Diameter D1 mm 105 105 105 105 115 115 140 150
Hole circle diameter D2 mm 75 75 75 75 85 85 100 110
Screw hole diameter D3 mm 14 14 14 14 14 14 18 18
Number of screw holes pcs 4 4 4 4 4 4 4 4
Working pressure Mpa 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5